Chapter 11 - FINlite Graphics Tool 
  
Using the FINlite Graphics Tool
153
Siemens Industry, Inc. 
 
125-3584T
 
 
2.  Click Publish. 
3.  The graphics files on Drive A can be backed up to the Internal Flash Drive (IFD) 
using the HMI.  
Default Graphics 
To set a default graphic for the panel: 
1.  When publishing the file, select the Default check box. 
2.  Select Drive A. 
NOTE: Default graphics can only be saved to the A:\ drive. If you select Drive B, FINlite 
will automatically change the selection to Drive A, graying out the Drive B row in the 
Drive table. 
  Click Publish. 
  FINlite will automatically rename the file to “default.fnl”. 
  When you connect to that panel from the Field Panel Web Server user 
interface, the graphic will display as the default graphic. 
NOTE: Because Device Template graphics are published to the 
Graphics\Application\AppID folder on the panel, rather than in the Graphics 
folder, they cannot be used as default graphics. See the 
Creating Device 
Template
 section for more information on Device Templates. 
 
Creating Device Templates 
You can create a graphics template from a single file for reuse with multiple FLN 
devices that have the same application ID. This is accomplished by using the 
Create 
Device Template 
 feature (also called 
relativizing a file
).  
To Relativize a Graphics File: 
1.  Create a graphics file using a background graphic and components.  
2.  Connect to a panel. 
3.  Bind points from one of the desired FLN devices to each of the components in the 
graphic. 
4.  From the File menu, select Create Device Template. 
  The Relativize Mapping window displays.