Chapter 13 - Troubleshooting 
Install, Upgrade, and Connection Errors 
174 
Siemens Industry, Inc. 
 
125-3584T
 
 
Field Panel Web Server User Interface Upgrade Fails 
Issue: A Field Panel Web Server User Interface upgrade fails.  
Solution: A User Interface upgrade requires approximately 2.7 MB. Before performing 
the upgrade, verify that Drive A has enough space. If necessary, delete the 
siemensviewer.swf and fpweb.swf files from the A:\wsroot folder. 
For information about deleting files via the HMI, see the 
Field Panel Features for Field 
Panel Web Server 
 section. 
Also, FTP can be used to add and remove files from the RAM drive. 
Browser Will Not Connect to the Panel 
Issue: The browser window displays an error message, or the browser connects to the 
Web Server, but only one panel in the navigation pane is active (the rest are grayed 
out).  
Solution: The browser must be configured to ignore the proxy settings for the panel 
names and/or IP addresses. This can be done in most browsers via the Options dialog 
box. For example: 
  In Internet Explorer: In the Tools menu, select Internet Options. On the 
Connections tab, click the Settings button. In the Proxy Server area, select the Use 
a proxy server check box and the Bypass proxy server checkbox. Click the 
Advanced button. In the Exceptions area, add the panel names and/or IP 
addresses being used. Separate entries with semicolons. Click OK.  
  In Firefox: In the Tools menu, select Options. On the Advanced tab, click the 
Network tab, and then the Settings button. Select the Manual Proxy Configuration 
option, and add the panel names and/or IP addresses being used. Separate 
entries with commas. Click OK. 
 
Be sure to verify with IT personnel, if necessary, before making this change.
Empty Browser Window 
Issue: The browser window displays an empty browser page. 
Solution: Install Adobe Flash Player Plug-in Version 10.1 or later. 
Error Accessing Panel Message 
Issue: Error Accessing Panel message displays: 
 
If one panel loses communication, the Error Accessing Panel message will 
display, indicating the name of the panel which has lost communication. If multiple