Chapter 5 - Point Commander 
  
Point Commander Application Overview
35
Siemens Industry, Inc. 
 
125-3584T
 
 
  
 
 
CAUTION 
Command points only when you know the possible effects of making a change.
Ideally, only command points when making temporary changes, such as setpoint 
changes, or when commanding modes of operation, such as DAY and NIGHT. It is 
inefficient to place a point in operator (OPER) command priority for long periods of time 
or permanently. 
  
The Field Panel Web Server Point Commander Application allows you to manually 
control a point and override the pre-established automatic controls in a PPCL program 
or the Scheduler application. 
Under normal operating conditions, allow the TALON® Automation System to control 
the building through programs such as PPCL, rather than relying on manual control. 
However, there may be special circumstances when it is necessary to take temporary, 
manual control of building operations. 
Commanding a point may be necessary under the following conditions: 
  Troubleshooting a control strategy. 
  Responding to an alarm that indicates a malfunctioning device. 
  Managing run-time totalization. 
  Performing preventive maintenance tasks. 
CAUTION: Always follow standard safety procedures when performing 
maintenance tasks. 
The Point Commander application window can be opened for a particular point object 
from the Device/Points application bar in the Navigation Pane, or from a Graphics View 
application tab. 
User Interface Description for the Point Commander 
Application 
The Commanding window can be accessed via the Device/Points bar in the navigation 
pane on the left side of the screen. Double click the point name (or single click the 
Command button to the right of the point name) to open the basic (default) 
Commanding window: