Chapter 11 - FINlite Graphics Tool
Using the FINlite Graphics Tool
155
Siemens Industry, Inc.
125-3584T
In the Field Panel Web Server User Interface
To apply the relativized graphics file to an FLN device:
1. Open the relativized graphics file.
1. Open the relativized graphics file.
Device Template graphics (relativized graphics files) are stored within the selected
panel in the Graphics area, by application ID (Graphics\Application\ApplicationID).
Because Device Template graphics are published to the Graphics\Application\AppID
folder on the panel, rather than in the Graphics folder, they cannot be used as default
graphics.
- A Select Device drop-down list will display in the Graphics Viewer on the right
side of the Web Server.
2. Select the device whose live data should display in the relativized graphic.
3. Click Go.
3. Click Go.
The relativized graphic will display the live data from the selected device.
Backing Up Graphics
Use this procedure to back up graphics files via the HMI.
HMI
S, H, E, W, G (System, Hardware, Ethernet, Webserver, Graphicsbackup
Example
10:13:04 07/30/2010 FRI Logged on successfully Field panel
<40091>
User: <high> <High default user account>
>Point, Application, Time, Message, Cancel, System, passWord,
Bye? s
>Diagnostics, Users, dSt, Bacnet, Error_msgs, Hardware, Text,
Quit? h
>Fieldpanels, Ethernet, nodeNametable, Disks, Reportprinter,
Licensemanager, Quit? e