Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual 
4  
Siemens Building Technologies, Inc. 
Controller LED Indicators 
The controller has several Light Emitting Diode (LED) indicators. (Figure 1). Table 2 lists the 
LED types and what they indicate. 
Table 2.  Controller LEDs.  
LED Type 
Label 
(if present)* 
Indication 
DO 
LED 1–LED 8 
Indicates the ON/OFF status of the DO associated with it. A 
glowing LED indicates that the DO is energized. 
Receive 
RX 
Indicates , when flashing, that the controller is receiving 
information from the field panel. 
Transmit 
TX 
Indicates, when flashing, that the controller is transmitting 
information to the field panel. 
Basic Sanity 
Test 
BST 
Indicates, when flashing ON and OFF once per second, that 
the controller is functioning properly. 
* Some LED labels may be hidden by the controller cover. 
Temperature Sensors 
An electronic Room Temperature Sensor (RTS) or an optional auxiliary temperature sensor 
may be used with the Siemens BACnet Heat Pump Controller—Multi-Stage. 
Room Temperature Sensor 
The controller room temperature sensor connects to the controller by means of a cable 
preterminated at both ends with a 6-conductor RJ-11 plug-in connector. See Figure 1 for the 
location of the RTS/Human-Machine lnterface (HMl) port. 
Mixed Air Temperature Sensor 
The mixed air temperature sensor is a 10K 
Ω thermistor that connects to the controller at Al 
5. 
For more information about Siemens temperature sensors, contact your local Siemens 
Building Technologies representative. 
Actuators 
The actuator used with the Siemens BACnet Heat Pump Controller—Multi-Stage may be an 
optional floating control or 0 to 10V spring return electronic damper motor that is powered 
through the controller to position an outside air damper. 
For more information about Siemens actuators, contact your local Siemens Building 
Technologies representative.