Point Database 
Siemens Building Technologies, Inc. 
 
23 
Description Address  Application 
Description 
DMPR POS 
{49} 
2583, 2584 
Current position of the damper motor in percent of full travel. 
This value is calculated based on motor run time. 
MTR1 POS 
{49} 
2590 
Current position of the damper motor in percent of full travel. 
This value is calculated based on motor run time. See 
MTR1 TIMING.
 
DO 8 
{50} 
2590 
Digital output 8 controls a 24 Vac load with an ON or OFF 
status. 
FAN 
{50} 
2583, 2584 
Digital output used to control the fan. ON indicates the DO is 
energized; OFF indicates the DO is de-energized. 
MTR TIMING 
51 
2583, 2584 
Time required for the damper actuator to travel from full 
closed to the full open position. 
MTR1 TIMING 
51 
2590 
Time required for the Motor 1 actuator to travel from full 
closed to the full open position. 
AI 3 
{52} 
2583, 2584, 2590 
Spare analog input, switch selectable to be 0-10V or 4-
20mA (consult your Siemens Building Technologies 
representative). Or, spare DI dry contact, see DI 3. The 
physical input can not be used for both analog and digital 
input at the same time. 
AI 4 
{53} 
2583, 2584, 2590 
Spare anolog input, 10K Ω thermistor. Or, spare DI dry 
contact, see DI 4. The physical input can not be used for 
both analog and digital input at the same time. 
AOV 2 
{54} 
2583, 2584, 2590 
Analog output 2 controls a 0 to 10V signal. 
DI 3 
{55} 
2583, 2584, 2590 
Actual status of a contact connected to the controller at  
Dl 3. ON indicates that the contact is closed; OFF indicates 
that the contact is open. When a contact is connected at Dl 
3, Al 3 is not available. See AI 3. The physical input can not 
be used for both analog and digital input at the same time. 
DMPR ROT ANG 
56 
2583, 2584 
Number of degrees the damper is free to travel. 
DPR1 ROT ANG 
56 
2590 
Number of degrees the damper is free to travel. 
DI 4 
{57} 
2583, 2584, 2590 
Actual status of a contact connected to the controller at  
Dl 4. ON indicates that the contact is closed; OFF indicates 
that the contact is open. When a contact is connected at Dl 
4, Al 4 is not available. See AI 4. The physical input can not 
be used for both analog and digital input at the same time. 
MTR SETUP 
58 
2583, 2584, 2590 
Configuration setup code for Motors 1 and 2. This enables 
the motors individually and sets each motor to be either 
direct or reverse acting.  
NOTE:
 When a motor is enabled, its associated DOs are 
enabled. 
DO DIR.REV 
59 
2583, 2584, 2590 
Configuration setup code for DOs. Allows the DOs to be 
direct or reverse acting (enabled equals energized or 
disabled equals de-energized).