SITRANS LU01 – INSTRUCTION MANUAL
Page 29
m
mmmm
Pa
ra
ra
m
e
te
rs
Quick Start (P001 to P007)
P001 Operation
Sets the type of measurement required for the application.
P002 Material
Specifies material type. If the material presents a flat surface perpendicular to the
transducer beam, select liquid.
P003 Maximum Process Speed
Determines level change reaction speed.
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
higher accuracy. Faster settings allow for more level fluctuations.
Values
0
Out-of-service
1
Level – how full the vessel is (Point 1 and/or 2 only)
2
Space – how empty the vessel is (Point 1 and/or 2 only)
3
*
Distance – distance from transducer to material (Point 1 and/
or 2 only)
or 2 only)
Values
1
*
Liquid or flat surface
2
Solid or angled surface
Alters
•
P830 TVT Type
Values
1
Slow (0.1 m/min)
2
*
Medium (1 m/min)
3
Fast (10 m/min)
4
Surge (1.7 m/sec)
5
Immediate (17 m/sec)
Alters
•
P070 Failsafe Timer
•
P700 Max Fill Rate
•
P701 Max Empty Rate
•
P702 Filling Indicator
•
P703 Emptying Indicator
•
P704 Rate Filter
•
P710 Fuzz Filter
•
P713 Echo Lock Window
•
P727 Scan Delay
•
P841 Long Shot Number
Related
•
Failsafe (P070 to P072)
•
Rate (P700 to P708)
•
Measurement Verification (P710 to P713)
•
Transducer Scanning (P726 to P729)
•
P905 Transmit Pulse