Functions 
 
3.4 Fieldbus interface 
 
M200D AS-Interface Basic 
22
 
Manual, 03/2009, A5E01668085-01 
3.4 
Fieldbus interface 
Response to CPU / master STOP 
If the fieldbus interface is interrupted, all control signals are set to 0. 
 
 
Note 
This is only relevant in "automatic" mode. 
 
 
Group diagnosis    
The controller is informed of whether or not a group fault message is present in the device 
when "I/O fault bits" on the SAP status tab (S1 = 1) is set. The AS-i master enters the S1 
value in the list of I/O faults (LPF) that have been signaled. The controller can read this list 
via the "GET_LPF" command and then query a specific diagnostic value from the slave (see 
also Diagnostics via parameter channel (parameter echo) (Page 84)). 
The motor starter issues a fault message if a fault is present. In this case, the SF LED lights 
up red. 
Reference 
For more information, refer to the documentation for your AS-i master.