Installation / connection 
 
4.1 Installation 
 
M200D AS-Interface Basic 
48
 
Manual, 03/2009, A5E01668085-01 
4.1.2 
Derating 
What is derating?   
Derating allows devices to be used even in severe operating conditions by selectively 
restricting the output capacity. 
Derating factors   
When M200D AS-i motor starters are operated under harsh conditions, the following factors 
must be taken into account: 
●  Ambient temperature T
u
:
 
 
–  The ambient temperature T
u
 is the temperature of the air surrounding the motor starter 
housing. 
The lower the maximum ambient temperature T
u
, the higher the current load on the 
motor starter can be. 
–  The installation position affects how quickly the motor starter cools. 
●  Absolute current load: 
–  The lower the current flowing through the motor starter, the lower the power loss 
(= heat) inside the device. If slight self-heating occurs, the ambient temperature T
u
 can 
be higher. 
–  In the case of soft starters in which the soft start function has been deactivated, the 
maximum permissible rated operating current I
e
 is restricted to 9 A (≡ electronic direct 
starter; sDSte).