Configuration / parameterization 
 
5.4 Process images 
 
M200D AS-Interface Basic 
74
 
Manual, 03/2009, A5E01668085-01 
5.4 
Process images 
Definition of process image   
The process image is a component of the AS-i master system memory. 
At the start of the cyclic program, the signal states of the inputs are transferred to the 
process image for the inputs.  
At the end of the cyclic program, the process image of the output is transferred to the slave 
as a signal state. 
Input process image (PII)   
The following table contains process data and a process image for inputs DI 0 to DI 3: 
 
Byte / bit  Process image  
Signal: 1 = HIGH, 0 = LOW 
DI 0 
Ready (automatic) 
0: Starter not ready for host / PLC 
1: Starter ready to be operated via host 
DI 1 
Motor ON 
0: OFF 
1: ON (CW / CCW) 
DI 2 
Input 1  
(input action: quick stop) 
0: Not active 
1: Active 
DI 3 
Input 2  
(no action) 
0: Not active 
1: Active 
Output process image (PIO)   
The following table contains process data and a process image for outputs DO 0 to DO 3: 
 
Byte / bit  Process image  
Signal: 1 = HIGH, 0 = LOW 
DO 0 
Motor RIGHT 
0: Motor OFF 
1: Motor ON 
DO 1 
Motor CCW 
0: Motor OFF 
1: Motor ON 
DO 2 
Disable quick stop 
0: Not active 
1: activated 
DO 3 
A / B switchover 
0: A slave activated 
1: B slave activated 
Reference 
For more information about system integration and data management in the controller, refer 
to the "System AS-Interface" 
(