Siemens Boating Equipment M200D 사용자 설명서

다운로드
페이지 114
Diagnostics 
 
7.2 Diagnostics with LED 
 
M200D AS-Interface Basic 
80
 
Manual, 03/2009, A5E01668085-01 
7.2 
Diagnostics with LED 
7.2.1 
Statuses of the individual LEDs 
The following LEDs indicate the status of the motor starter:   
'(9
6)
67$7 3:5
$6L
)$8/7
$8;
3:5
 
SF LED (possible colors: red / OFF)   
 
Status 
Meaning 
Dependencies 
OFF 
No fault 
 
Device fault 
• 
Current flowing with no ON command 
• 
Self-test fault 
Red 
Device detects fault 
Device detects system fault: 
• 
Residual current detected 
• 
No U
AUX
 
• 
External encoder supply short-circuit 
DEVICE LED (possible colors: red / green / yellow / OFF)   
 
Status 
Meaning 
Cause 
OFF 
Device not ready 
System fault:  
• 
No supply voltage for electronics or power 
supply is < 18 V 
Green 
Device ready 
— 
Flashing green 
Device not starting 
Device not initialized in factory or no startup 
parameters received (parameter bits from master)
Yellow 
Internal trip 
— 
Flashing yellow 
Group alarm 
The device has detected a system fault and 
issues a group alarm due to: 
• 
Prewarning limit of thermal motor model being 
exceeded 
• 
Incorrect parameter value: 
therm. motor model + temperature sensor 
deactivated (motor protection deactivation 
rule) 
Red 
Device defective 
A device defect was detected during the self-test.