12.2 Parameter list
Display
Parameter designation
Range of values (default values)
Range of values (default values)
Gradient, flow
0.2 to 3.2 (1.8)
Level, flow
–30 to 30 °C (0 °C)
4-point characteristic
Press key to set parameters
outdoor temperature, points 1 to 4
flow temperature, points 1 to 4
return flow temperature, points 1 to 4
flow rate, points 1 to 4,
capacity, points 1 to 4.
outdoor temperature, points 1 to 4
flow temperature, points 1 to 4
return flow temperature, points 1 to 4
flow rate, points 1 to 4,
capacity, points 1 to 4.
4-point characteristic, outdoor temperature
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
below the numbers 2, 3, 4.
–30 to 20 °C
( point 1: –15 °C, point 2: –5 °C, point 3: 5 °C, point 4: 15 °C)
( point 1: –15 °C, point 2: –5 °C, point 3: 5 °C, point 4: 15 °C)