Final Installation
23
Final Installation
Now that you have completed Configuration you are ready to
connect the SNMP Solo to your UPS and to the network. Follow
these steps to complete the installation:
1. 
Turn DIP switch 1 on the SNMP Solo from the DOWN
(ON) position to the UP (OFF) position.
2. 
Disconnect the configuration cable from the SNMP Solo
adapter and the terminal or PC. Store this cable for
future use.
3. 
Disconnect the SNMP Solo from the power supply.
4. 
Locate the cable labled “73743”. This is the UPS
interface cable. Place the SNMP Solo close enough to
the UPS so the UPS interface cable can connect the
SNMP Solo’s serial port and the UPS’s serial port.
5. 
Connect the labelled end of the UPS interface cable to
the SNMP Solo’s serial port. Connect the other end to
the UPS’s serial port.
6. 
Connect the SNMP Solo to the Ethernet cable—either
UTP or BNC.
7. 
Reconnect the SNMP Solo to the power supply.
Verify the SNMP Solo Operation
After you complete all configuration settings and connect the
SNMP Solo to the network, check the LINK status.
LED Status After Power Up
At first, green and red LEDs do not light.
Green LED begins to pulse randomly, showing
network activity.
Five to ten seconds after power up, the red
LED flashes rapidly; this indicates that the
SNMP Solo is determining which UPS model is
connected to your system.
After SNMP Solo determines your UPS model,
the red LED turns off.
The red LED pulses once whenever the SNMP
Solo detects a communication failure.