Parker Products COMPAX-M /-S (L) 사용자 설명서
Operating Instructions
COMPAX-M / -S
PLC data interface (function not available with COMPAX 1000SL)
158
Start sign
"E"
≡
"1110"
Function code 1: "1"
≡
"0001"
Function code 2: "3"
≡
"0011"
Parameter No. tens column
Parameter No. digits column
Assignment code: "A"
Parameter No. digits column
Assignment code: "A"
≡
"1010"
Sign "0"
≡
"0000": positive
"D"
≡
"1101": negative
Numerical value 10
6
Numerical value 10
5
Numerical value 10
4
Numerical value 10
3
Numerical value 10
2
Numerical value 10
1
Numerical value 10
0
Decimal point
"C"
≡
"1100"
Numerical value 10
-1
Numerical value 10
-2
End sign
"F"
≡
"1111"
Start sign
"E"
≡
"1110"
Function code 1: "1"
≡
"0001"
Function code 2: "4"
≡
"0100"
End sign
"F"
≡
"1111"
Start sign
"E"
≡
"1110"
Function code 1: "1"
≡
"0001"
Function code 2: "6"
≡
"0110"
Numerical value 10
1
Numerical value 10
0
End sign
"F"
≡
"1111"
Start sign
"E"
≡
"1110"
Sign "0"
≡
"0000": positive
"D"
≡
"1101": negative
Numerical value 10
6
Numerical value 10
5
Numerical value 10
4
Numerical value 10
3
Numerical value 10
2
Numerical value 10
1
Numerical value 10
0
Decimal point
"C"
≡
"1100"
Numerical value 10
-1
Numerical value 10
-2
Numerical value 10
-3
End sign
"F"
≡
"1111"
The following signs are not necessary when transferring:
♦
Positive prefixes and initial zeros.
♦
For whole number values: the decimal point and the figures after the decimal
point.
Modify
parameters
P1...P49
parameters
P1...P49
Acceptance of VP
parameter
parameter
Status query
S1...S12 (actual
values)
S1...S12 (actual
values)
Status response
S1...S12 (actual
values)
S1...S12 (actual
values)