Parker Hannifin 6K 사용자 설명서

다운로드
페이지 47
NTIO
 command to specify the type of module in that position.  
 
                                              
n
 
\
 
m
 
NTIO
 
<i>
Module # on Server “n
Range: 0-7
Network Server #
Range: 1-6
Module Type. Options are:
1 = Digital/Discrete Inputs
2 = Digital/Discrete Outputs
3 = Analog Inputs
4 = Analog Outputs
 
 
For example, if there is a digital input module in slot 0, then the command would be 
3\0NTIO1
. If there is an Analog Input module in slot 7, then the command would be 
3\7NTIO3
.  
7.  Set the polling rate with the 
NTPOLL
 command. 50 milliseconds is recommended. For 
example, to set the polling rate to 50 ms on server #3, use the 
3NTPOLL50
 command. If 
there is an error during polling, then Error Status bit #24 will be set.  
Example 
NTADDR172,34,54,123   ; Set the IP address of the 6K 
OPTEN0                ; Disable the option card (for Fieldbus units only) 
RESET 
NTFEN2                ; Enable network function on 6K 
RESET 
 
DEL OPTOSU 
DEF OPTOSU 
2NTIP2,172,34,54,124  ; Identify an OPTO22 device as Server #2, which is  
                      ; located at IP address 172.34.54.124 
2NTCONN1              ; Attempt connection to Server #2 (OPTO22)  
2\1NTIO2              ; Configure OPTO22 module 1 as digital output 
2\2NTIO2              ; Configure OPTO22 module 2 as digital output 
2\3NTIO1              ; Configure OPTO22 module 3 as digital input 
2\4NTIO3              ; Configure OPTO22 module 4 as analog input 
2NTPOLL50             ; Begin polling, set polling interval to 50 ms 
END 
Program 
Interaction 
Once the OPTO22 is configured and a connection is made, you can then set outputs and check 
inputs. 
How the 6K addresses OPTO22 I/O locations: 
The 6K addresses each I/O bit by its location on a specific module. (NOTE: I/O points are 
not addressed by an absolute 32-bit location on the OPTO22.) Digital input and output 
modules have four I/O points, or channels, and are numbered 1-4. Analog input and output 
modules have two I/O points, or channels, and are numbered 1-2. 
Digital
Input
Module
Input
1
0
Input
2
Input
3
Input
4
Digital
Input
Module
Input
1
1
Input
2
Input
3
Input
4
Digital
Output
Module
Output
1
2
Output
2
Output
3
Output
4
Digital
Output
Module
Output
1
3
Output
2
Output
3
Output
4
Analog
Output
Module
Output
1
4
Output
2
Analog
Output
Module
Output
1
5
Output
2
Analog
Input
Module
Input
1
6
Input
2
Analog
Input
Module
Input
1
7
Input
2
EXAMPLE: OPTO22 is Network Server #3
3\0IN.3
3\3OUT.2
3\5ANO.1
3\7ANI.2
 
 
•  To verify the I/O configuration (as per 
NTIO
) and to check the status of each module’s 
inputs and outputs, type 
n
\TIO
, where “
n
” is the server number.  
•  To set a digital output, type 
n
\
m
OUT.
i
-
b
, where “
n
” is the server number, “
m
” is the 
module number, “
i
” is the point number on that module and “
b
” is the state (
1
 = on, 
0
 = off). To set multiple digital outputs on the same module, type 
n
\
m
OUT
bbbb
 
O t t #1
page 10