Introduction
Connected to the CT-V900 controller’s expansion bus, the 
2-Door Expansion Module (CA-A470-A) supports two 
readers, two BCD keypads, four zone inputs, 6 outputs 
and two locking devices. 
Specifications
DIP Switches 
In order for new DIP switch settings to take effect, 
the 2-Door Expansion Module’s power must be 
disconnected and then reconnected.
Assign Address (1 and 2)
DIP switches 1 and 2 determine the 2-Door 
Expansion Module’s address in the network, 
regardless of the order that they are connected 
to the controller. Centaur recognizes the doors 
according to the DIP switch settings as shown in 
Figure 1.
Figure 1: Setting the network address
Lock State during Communication Failure
DIP switches 3 and 4 determine the state of 
Lock #1 and Lock #2 ONLY during a 
communication failure between the 2-Door 
Expansion Module and the controller (CT-V900-
A). Normally, the lock outputs follow the Lock 
Control for the CT-V900-A. Therefore, the DIP 
switches should have the same setting as the Lock 
Control for the corresponding doors in Centaur.
De-energized: no power in normal state; requires 
power to activate.
Energized: power in normal state; remove power 
to activate.
Access during Communication Failure (5 and 6)
DIP switches 5 and 6 determine the access to 
the protected doors during a communication 
failure. 
Activate Output on Communication Failure (7)
DIP switch 7 determines if OUT5 and OUT6 will 
pulse during a communication failure. When DIP 
switch 7 placed in the 
ON
 position, the outputs on 
the device(s) connected to the OUT5 and OUT6 
terminals will pulse. For example, the LED on 
the reader can pulse to advise users that a 
communication failure has occurred.
DIP Switch (8)
For future use.
EOL Jumper
Place the EOL jumper ON if the 2-Door Expansion Module 
is at the beginning (Start Point) or at the end (End Point) of 
the E-bus Network (see Figure 2). Otherwise, place the 
EOL jumper OFF.
Figure 2: Setting the Jumpers
High/Low Bias Jumpers
Place the A+ and B- jumpers on LOW only if the 2-Door 
Expansion Module is at the beginning (Start Point) of the 
E-bus Network. Otherwise, place the A+ and B- jumpers 
on HIGH (see Figure 2 and Figure 3).
Figure 3: Setting the A+ and B- jumpers
350mA/700mA Battery Charging Jumper
The 350mA/700mA Jumper allows you to select the 
charging current for the backup battery of the 2-Door 
Expansion Module. Charging the battery at 350mA takes 
longer, but consumes less power. Charging the battery at 
700mA takes less time, but consumes more power.
Figure 4: Setting the 350mA/700mA jumper
Programming in Centaur
Using the Centaur Access Control Software, program the 
inputs, outputs, readers, and keypads connected to the 2-
Door Expansion Module. The options are explained in the 
Centaur Access Control Software Reference Manual
Centaur will identify the 2-Door Expansion Module by its 
address (see DIP Switches 1 to 4) and will recognize the 
devices as follows: 
Doors cannot be defined as Door Type Elevator 
(Door Properties window, General tab, Door 
Type
Elevator) and the module does not support 
Interlock Inputs (Door Properties window, Inputs 
and Outputs
 tab, Interlock Input). 
Other modules in the system cannot activate the 2-
Door Expansion Module’s outputs.
The 2-Door Expansion Module does not support 
Zone Doubling (see Figure 6).
CA-A470-A Specifications: 
Readers:
connect 2 per module
Keypads:
connect 2 per module
Inputs: 
4 standard without ATZ, 1 tamper
Outputs:
6 (open collector)
Lock Outputs:
2 lock outputs (Form C relays)
each: 15A @ 16VDC (resistive)
AC Power: 
16VAC, 40VA max.
Frequency:
50Hz/60Hz
Aux. Current:
500mA (max.)
Battery:
12VDC, 7Ah
low battery = 10.2VDC
low battery restore = 12.2VDC
low battery cut-off = 8.5VDC
Communication:
expansion bus (E-Bus), RS-485, Plug 
and Play, 3 modules per CT-V900
Operating temp.: 5
o
C to 55
o
C (41
o
F to 133
o
F)
2-Door Expansion Module
CA-A470-A
Instructions
780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA
Tel.: (450) 491-7444                                       Fax: (450) 491-2313
www.paradox.ca
Lock #1 = DIP switch 3
Lock #2 = DIP switch 4
OFF =
De-energized:
During a communication failure, the normal state of
the lock output is De-energized. When Lock #1 or
Lock #2 is activated, power is applied to the
corresponding lock output to unlock the door.
Activation depends on the setting of the DIP switches
5 & 6 (Access during Communication Failure).
ON =
Energized:
During a communication failure, the normal state of
the lock output is Energized. When Lock #1 or Lock
#2 is activated, power is removed from the
corresponding lock output to unlock the door.
Activation depends on the setting of the DIP switches
5 & 6 (Access during Communication Failure).
Switch Setting
During a Communication Failure:
5 = off (0)
6 = off (0)
“No Card” 
Access is denied to all cards and doors
are locked until communication is restored.
5 = on (1)
6 = off (0)
“2 Cards” 
Access is granted only when 2 cards of
a valid format are presented to the reader.
5 = off (0)
6 = on (1)
“All Cards” 
Access is granted when any card with
a valid format is presented to the reader.
5 = on (1)
6 = on (1)
“Unlock Door”
Doors are unlocked until communication
is restored.
Address 1 Address 2 Address 3
Doors
Keypad/Reader 1 Door 3
Door 5
Door 7
Keypad/Reader 2 Door 4
Door 6
Door 8
Inputs
Z1
Input 17
Input 21
Input 25
Z2
Input 18
Input 22
Input 26
Z3
Input 19
Input 23
Input 27
Z4
Input 20
Input 24
Input 28
Outputs
OUT1
Output 7
Output 13
Output 19
OUT2
Output 8
Output 14
Output 20
OUT3
Output 9
Output 15
Output 21
OUT4
Output 10
Output 16
Output 22
OUT5
Output 11
Output 17
Output 23
OUT6
Output 12
Output 18
Output 24
Jumpers set to low
Jumpers set to high
A+
B-
LOW
HIGH
LOW
HIGH
A+
B-
Jumper set 
as 350mA
Jumper set 
as 700mA