3. Installation 
Make sure the location satisfied the requirements listed under Storage and Installation 
Location   (page 3) and check the dimensions using the diagrams in other catalogs or external 
view diagrams and panel cut diagram. Prior to installation, the maximum fault current capacity 
of the power system at the point of installation should be verified. This value must not exceed 
the symmetrical interrupting capability of the circuit breaker. See typical circuit breaker 
nameplate below. 
 
Do not exceed the ratings specified on the breaker nameplate or 
system accessories. Underrated equipment can fail during operation 
causing fire, explosion, severe injury, death, and property damage. 
 
 
 
 
            Typical Circuit Breaker Nameplate 
3.1 Mounting the VCB 
3.1.1 Mounting in the panel 
The standard panel thickness is t3.2. Consult Toshiba when using with other thicknesses. 
To mount the VCB, perform the steps shown in Figures 8 through 10 in that order, referring 
to the tightening torque in Table 5. 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 7 Remove the four (4) panel 
mounting bolts (M8) and two (2) pan-head 
screws (M4) from the VCB.
 
Figure 8 Align to the panel holes 
and mount the VCB with two (2) 
upper bolts on the panel.
 
       
DANGER