- 17 - 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3.3 Ground Terminal Connections 
The ground terminal is on the left side of the terminal block as viewed from the rear of the VCB. To 
connect the ground line to the terminal, perform the steps shown in Figures 21 and 22 in that order. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3.4 Control Circuit Cable Connections 
 
 
Screw Tightening 
torque 
M8 
11.8 – 14.7 N m 
(120 – 150 kgf cm) 
M10 
24.5 – 30.9 N m 
(250 – 315 kgf cm) 
M12 
44.1 – 55.4 N m 
(450 – 565 kgf cm) 
Figure 21 Crimp the ground line to the 
crimp-on terminal provided with the unit.
 
Figure 22 Fasten the crimped terminal 
using the hexagonal bolt (M8) provided 
with the unit. 
 
Figure 23 The control circuit is connected to 
the terminal block on the top of the operating 
mechanism. Connect as shown in the 
connection diagram in section 4.3. 
 
Figure 20 Set the insulating cylinder in place, then
check to make sure that the hook is engaged.
 
Table 6 Tightening torque 
CRIMP