Optiquest iRIS 220 사용자 설명서

다운로드
페이지 73
 iRIS 220 / iRIS 320, V1.19 User Guide - 56 
 
56
 
iQuest (NZ) Ltd  - PO Box 15169, Hamilton, New Zealand  Tel: +64 7 857-0810  Fax: +64 7 857-0811  Email: iquest@iquest.co.nz
 
 
  -               + 
External  
12V Battery 
(Optional) 
DN
 
Up/Down 
UP
 
Water Level                                                    
+12V
 
 Sensor 
0V
 
 
AI4  
AI3  
AI2  
AI1  
AGND  
5VOP  
DI2  
DI1  
DO2  
DO1  
SDI-12  
DGND 
12V+  
GND (-)  
VIN+  
GND (-) 
 
6.4 Connecting an Up/Down Water Level Instrument 
 
A relatively common type of digital water level instrument is one that provides two pulse outputs. One output 
generates a pulse for each increment and the other for each decrement in level. The iRIS maintains a record 
of these steps and therefore the relative level. 
 
These  instruments  normally  require  a  12V  supply  and  this  is  readily  obtained  from  the  iRIS.    A 
supplementary 12V battery can be connected if desired. Typically, this type of instrument requires very little 
current, so the internal iRIS 320 battery will normally suffice.   
 
The diagram below shows the required connects for such an installation.  The incrementing output must be 
connected to DI1 and the decrementing output to DI2. 
 
 
TOP 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
BOTTOM 
 
iRIS I/O Connector
 
 
 
 
Charging source 
 e.g solar panel