 iRIS 220 / iRIS 320, V1.19 User Guide  
 
 
2 Overview 
2.1 Introduction 
The iRIS 220 and iRIS 320 (iQuest Remote Information Source) are two related products that share similar 
electronic components and operate in much the same way.  They have been designed as cost effective, low 
power, self contained information sources for use in a wide range of data gathering and logging applications.   
 
Both models achieve GPRS or CDMA network connectivity through the use of an integral wireless modem. 
Depending on the application and target market, this modem will be one of the following: 
 
 
Dual-band 900MHz/1800MHz GSM/GPRS 
 
Single-band 1900MHz GSM/GPRS 
 
CDMA/CDMA-1X 
 
This modem also supports the alternative GSM or CDMA connection options of CSD (Circuit Switched Data) 
and  SMS  (Short  Message  Service).  These  options  require  the  appropriate  service  to  be  enabled  by  the 
wireless service provider. 
 
The  two  units  differ  primarily  in  their  available  features  and  also  the  enclosure  design.    The  following  two 
sections explain the key differences between the two models. 
 
 
2.2 General Characteristics – iRIS 220 
 
The iRIS 220 is supplied in a lightweight extruded aluminium enclosure finished in a resilient powder coating.  
This enclosure provides mechanical strength and EMI shielding, and also enables easy mounting in a variety 
of situations.   
 
The iRIS 220 supports a maximum of six external sensors (1-6). Sources for these sensors may be chosen 
from  physical  digital  or  analog  inputs  or  virtual  sources  (via  serial  communication  or  internal  calculations).  
Each sensor has two associated alarms, each with separate trigger and reset levels.  Each alarm also has a 
duration,  which  is  used  to  delay  the  alarm  trigger  for  analog  inputs  and  to  determine  the  time  over  which 
pulse input counters should be totalised (for rainfall etc).   
 
Three additional sensors (7-9) are reserved for internal measurements (battery voltage, supply voltage and 
logger temperature).  Data from all enabled sensors are logged in a four word (8 byte) compressed format 
which includes full date and time to fractions of a second. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 1 - iRIS 220