Chapter 2
Function Reference — DIG_Block_In
©
 National Instruments Corporation
2-151
NI-DAQ FRM for PC Compatibles
you must use the value of alignIndex return by 
Align_DMA_Buffer
 to access your data. In 
other words, data in an aligned buffer begins at buffer[alignIndex]. Data in an unaligned 
buffer begins at buffer [0].
Note
DIG_Block_In
 will not work with groups of size = 1, because of a DMA limitation 
when using the AT-DIO-32F.
Note
If you are using an SCXI-1200 with remote SCXI, count is limited by the amount 
of memory made available on the remote SCXI unit. For digital buffered input, 
you are limited to 5,000 bytes of data. The upper bound for 
count depends on the 
groupSize set in 
DIG_SCAN_Setup
 (for example, if groupSize = 2, count 
 2,500).