11.4  
PANEL FUNCTIONS (STANDARD OR BLC OUTPUTS)
The panel functions option defines parameters for the basic loop controller BLC sounder and relay outputs.
Panel functions can be programmed from the following locations:
!
 
Using the panel menu, BLC outputs is located at Set  → Standard features → BLC Outputs →
followed by the required output to be programmed.
!
 
Using the VIPER software, Panel Functions (Std Outputs) is located at Edit →Standard features →
Panel functions (STD outputs)
The following Table 13 details the options available:
STANDARD FEATURES – PANEL FUNCTIONS
Option
Function
Location \ type
Describes the type of BLC monitored circuit or relay output located within the control panel.
Custom type
Default text describing the individual output type and can be changed to 1 of 50 pre-programmed (12 character
max) custom text messages. Custom type messages are entered from the custom features menu.
Text message
A 24-character text message can be entered to describe the use of the individual output circuit. Example
MBLC01 Scct1 = Sounders Ground Floor, MBLC01 VFCO1 = Fire Brigade Link
Group Number
Default set at CMN (common alarm) operating on any fire condition. To configure as programmable, set BLC
output circuits and relay contacts to an output group number. Range 1 to 500. Note: Output Groups 501 to 512
are reserved for special functions and should not be used for general cause \ effect programming. Each output
group may contain one or more devices or modules. Devices default to group 000.
Manual Sound
Associated to the common alarm operation. Set to ‘Yes’ to allow the output circuit to operate when the control
panels ‘Evacuate’ button is pressed.
Clear
Associated to the common alarm operation. Determines whether the output will switch off when the panels
‘Silence Alarm’ button or ‘Reset’ button is pressed.
Table 13: Standard Features – Panel Functions
11.5   
OUTPUT GROUP INFORMATION
The output group information option defines parameters for the software programmable output groups. There
are 512 programmable output groups available to create a site-specific cause / effect evacuation strategy.
Output Groups 501 to 512 are reserved for special functions and should not be used for standard programming.
Panel functions can be programmed from the following locations:
!
 
Using the panel menu, Output group info is located at Set → Standard features → Output group
info →
 followed by the required output group number to be programmed.
!
 
Using the VIPER software, Output Group Information is located at Edit  →Standard features →
Output Group Information
.
The following Table 14 details the options available:
STANDARD FEATURES – OUTPUT GROUP INFORMATION
Option
Function
Text message
A 24-character text message should be entered to describe the location within the building for the output
sounders & modules that are associated to the individual output group. Example Group 1 = Sounders Ground
Floor, Group 2 = Sounders Second Floor,  etc
Group action
Output groups can be assigned to one of the following command actions, Programmable (Program), Common,
Silence or Reset.
!
  Set to Program to specify which fire zones to be specified to operate the output group.
!
  Set to ‘Common’ to operate outputs associated to the group during any fire condition raised on the control
panel.
!
  Set to ‘Reset’ operates output(s) associated to output group for approximate time delay period specified in
T3 after operation of panel ‘Reset’ button by the user.
!
  Set to ‘Silence’ operates output(s) associated to output group for approximate time delay period specified
in T3 after operation of panel ‘Silence Alarm’ button by the user.
Manual sound
Set to ‘Yes’ to allow the output group to operate when the control panels ‘Evacuate’ button is pressed.
Clear
Determines whether the output group will switch off its associated output modules when the panels ‘Silence
Alarm’ button or ‘Reset’ button is pressed.
T3
Delay
Determines the Delay time period to the operation of output modules associated to the output group. Each
individual group has a delay time available from 000 to 600 seconds.
T4
Alert delay
Determines the Alert delay time period where sounders and output modules will provide a pulsing output
condition for the specified time period before switching to constant alarm condition. Each individual group has
an alert timer available from 00 to 60 minutes or select INF for infinite continuous pulsing until the system is
silenced or reset.