Kidde Fire Systems VEGA LT TM0081 사용자 설명서

다운로드
페이지 51
TM0081      
Page 50 of 51
 Issue 1.01
Bad loop Count
The quantity of loop cards located within the
control panel is different to that specified
within the panel set up option.
Faulty BLC or Loop card. OR
BLC Communications failure. OR
New BLC recently installed.
Replace faulty boards.
Check panel set-up (refer section 11.1) and
log the detection loop (refer section 10.4 &
10.5)
Device
Unregistered
A device has been reported by the MBLC
card, which does not appear in the panel
memory.
Device added to system without power down
or auto-learn.
Faulty device – possible device answering to
address that is not connected to the loop.
Check detection loop wiring against as
fitted system drawings.
Locate and replace faulty device.
Loop fault
Open or short circuit on loop. Wiring problem,
Faulty loop card or device.
Check detection loop wiring. Replace faulty
loop card or device.
Double Address
fault
2 or more devices on a loop with the same
address. Wrongly addressed devices. Faulty
Device responding to wrong address.
Check detection loop wiring against as
fitted system drawings. Note: Base LEDs
operate on Apollo double addressed
devices.
Table 21: Panel Fault Diagnosis
Repeater Panel Messages
Message
Cause
Action
Polling Failure –
type 2 repeater
only
The repeater panel has failed to
communicate with main control panel.
Main panel is not addressing the repeater
panel correctly.
Repeater wrongly addressed or noise
induced on communication wiring.
Active repeaters not installed in panel set
up.
Check external wiring for induced noise.
Check Repeater panel address switch
settings.
Check panel set-up.
Repeater Off-line
– type 1 and 2
The repeater panel is not receiving data
from the main control panel.
Communication cable-wiring fault.
Faulty communications device or Faulty
board.
Repeaters not installed in panel set up
Check external wiring.
Check panel set-up.
Replace faulty cards.
Table 22: Repeater Panel Fault Diagnosis
16.  RECOMMENDED SPARES LIST
Description
Part Number
Box Assembly
43782-K143
Membrane Fascia
39155-K049
Master Control Processor (MCP)
44782-K071-03
Master Basic Loop Controller (MBLC)
44782-K073-02
Loop Card
44782-K074
LED Indication Card
44782-K170
Power Supply Unit 2.5 amp
28730-K002
Graphic LCD Display
43782-K141
Logo Plate (Blank)
50-100079-205
Harness MCP – MBLC
43682-K032
Harness MCP – MBLC
43682-K037
Table 23: Recommended Spares List