Wiring
All field installed wiring must be done in accordance with the
National Electrical Code ANSI/NFPA 70 – Latest Edition or
Canadian Electrical Code CSA C22.1 Part 1 or local codes. Unit
must be electrically grounded according to these codes. See
wiring diagram shipped with unit. For optional wiring diagrams
see Bulletin 6-443.
The power to these unit heaters should be protected with a
circuit breaker. Units for use with single-phase electric power,
should be provided with a manual motor starter, having properly
sized overload protection. Units for use with three-phase
electric power must be provided with a motor starter having
properly sized overload protection.
Location of thermostat should be determined by heating
requirements and be mounted on an inside wall about 5' above
floor level where it will not be affected by heat from the unit or
other sources, or drafts from frequently opened doors. See
instructions packed with thermostat.
Installation of Blower Models (BAE UNITS)
Attachment of Field Installed Ductwork, Blower
dels (BAE) Models Only
Burned-out heat exchanger as well as shorter equipment life will
result from not providing uniform air distribution.
When installing heater always follow good duct design practices
for even distribution of the air across the heat exchanger.
Recommended layouts are shown below. When installing
blower units with ductwork the following must be done.
1. Provide uniform air distribution over the heat
exchanger.
Use turning vanes where required. See figures below.
2.  Provide removable access panels in the ductwork on the
downstream side of the unit heater. These openings should
be large enough to view smoke or reflect light inside the
casing to indicate leaks in the heat exchanger and to check
for hot spots on exchanger due to poor air distribution or
lack of sufficient air.
3. If ductwork is connected to the rear of the unit use Modine
blower enclosure kit or if using field designed enclosure maintain
dimensions of blower enclosure as shown on page 12.
6
A
BAFFLE
B
12"
MIN.
A
B
BAFFLE
TURNING
VANES
12" MIN.
B
3" MAX.
TURNING
VANES
3" MIN.
A
A
3" MIN.
12"
MIN.
3" MAX.
TURNING
VANES
12"
B
BAFFLE
A
B
12"
MIN.
12"
MIN.
TURNING
VANES
INSTALLATION
Recommended Installations
SIDE VIEW
SIDE VIEW
TOP VIEW
SIDE VIEW
SIDE VIEW
TOP VIEW
Dimension “B” Should Never
Be Less than 1/2 of “A”
C
B
A
F
E
D
CAUTION
Disconnect  power  supply  before  making  wiring  connections
to  prevent  electrical  shock  and  equipment  damage.  ALL
UNITS  MUST  BE  WIRED  STRICTLY  IN  ACCORDANCE
WITH WIRING DIAGRAM FURNISHED WITH UNIT.
ANY  WIRING  DIFFERENT  FROM  WIRING  DIAGRAM  MAY
BE HAZARDOUS TO PERSONS AND PROPERTY.
Any damage to or failure of Modine units caused by incorrect
wiring of the units is not covered by MODINE’S STANDARD
WARRANTY (see Back Cover).
!
CAUTION
Proper  air  flow  and  distribution,  across  the  heat  exchanger
must  be  provided  to  prevent  early  failure  of  the  blower  unit
heater.
!
CAUTION
Do  not  attempt  to  attach  ductwork  of  any  kind  to  propeller
PAE models.
!
CAUTION
Check  for  red  heat  exchanger  tubes.  If  bottom  of  tubes
become  red  while  blower  unit  is  in  operation,  check  for
proper air volume and air distribution. Adjust blower speed or
correct discharge duct design to correct problem.
!