MGE UPS Systems 66074 사용자 설명서

다운로드
페이지 69
www.mgeups.com
Network
Management Cards
User Manual
T H E   U N I N T E R R U P T I B L E   P O W E R   P R O V I D E R
Network Management Card
 – User Manual
34003676EN/GA
Page 
19/69
3.2.6  Shutdown parameters
Click on the “Shutdown parameters” section in the menu to see the list of parameters. 
Important note:
For installations that do not use Network Shutdown Module (backup units, routers and other internetworking
equipment, automated systems, etc.) or in the event of long backup periods, the card will send a command to
the UPS to shut off end of the programmed Shutdown After time. To prevent this, the Shutdown After box
must be not selected (default) 
This page enables viewing and configuration of UPS operation parameters in battery mode and for power
restoration.
 When you tick the Show advanced parameters option, extra parameters are displayed.  These parameters
enable, in particular, adjustment of certain thresholds related to the percentage of remaining battery charge
level.
The Output column enables each output to be named (maximum 30 characters). 
Note
Priority is given to the main outlet, so the card does not accept configurations where the auxiliary outlets can be
supplied while the main outlet is switched off 
For the main outlet (Master)
Shutdown after is the operating time in minutes left for users after a switch to backup before starting
the shutdown sequences of the UPS and its equipment (from  0 to 1092).
If remaining time under (from 0 to 9999 seconds) and If Capacity under (from 0 to 100%) are two
extra conditions for remaining backup time and battery level that can trigger shutdown sequences
before the “Shutdown after” period runs out 
Shutdown duration is the time required for complete shutdown of systems when a switch to backup
time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum
of Shutdown duration of subscribed clients but can be modified in the Advanced mode