Remove : Depending on the kind of application, the selected ones will definitively disappear from the table
as SNMP applications, or they will disappear and automatically re-subscribe as the Network Shutdown
Module application.
Utility failure Test : Two alarms 'Utility failure' and 'Utility restored' spaced of 60 seconds will be sent to the
applications selected, making sure that the applications can be reached over the network.
Shutdown Test : This test simulates a UPS on battery operation, it sends alarms to the selected
applications. It enables an easy check to see if the server protection works correctly.- No intervention on
the UPS is required.
- Simulated alarms will be processed by the applications selected only.
- Warning :This test will generate a REAL shutdown sequence of servers on which Network Shutdown
Module is running.
Add NMS allows to add a SNMP trap receiver as a Network Management System.
Modify NMS allows to modify a SNMP trap receiver.
Both buttons makes appear a new window where it is possible to enter the Application name, the
Hostname or IP Address, the Trap community and the severity.
 
Trap community indicates the name of the SNMP community 
For more details, read the MIB description document: 34003627zjaa.pdf , available in the 
 site.
3.5.4  Central Shutdown Configuration
Click the “Notified Application” section in the menu then in “Configuration”.