3.6.3  Environment Settings 
The environment sensor measures temperature, humidity and gives the status of the 2 contacts (used for door,
alarms or generator unit).
The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of
the protected system.
The Sensor name is the function name given to the sensor, usually it enables location of the sensor. 
Temperature: choose the temperature unit (°C or °F)  from the selection box.
High threshold: if this value is exceeded, a notification is sent if this is validated. Default value is 40 °C / 104
°F.
Low threshold: if this value is exceeded, a notification is sent if this is validated. Default value is 5 °C / 41 °F.
Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold.
Default value is 2 °C / 3.6 °F. (Advanced parameters)
The high alarm cannot be reactivated while temperature remains above the High threshold – Hysteresis
value.
The low alarm cannot be reactivated while temperature remains below Low threshold + hysteresis  value.
Humidity
High threshold:
 if this value is exceeded, a notification is sent if enabled. Default value is 90%.
Low threshold: if this value is exceeded, a notification is sent if enabled. Default value is 5%.