HP Performance Optimized Data Center (POD) 40c 사용자 설명서

다운로드
페이지 84
 
Component identification  14 
Control cabinet component identification 
 
 
Item 
Component 
Description 
VESDA air sampling smoke 
detection unit 
An early warning laser scan smoke detection unit 
VESDA power supply with 
battery backup  
Provides power to the VESDA and backup power to the VESDA 
during a utility power loss 
Fire alarm and suppression 
release control panel 
 
Controls all fire systems within the HP POD 40c G2, including 
the smoke detection system, fire suppression system, fire pulls, 
and so on 
 
Includes a battery backup system that provides backup power 
to the fire system during a utility power loss 
Customer connection box 
Controls and organizes information monitored by the HP POD 40c 
G2 security components 
ECS relays and ECS modules 
Relays for the ECS control, ECS communications, I/O connections, 
and terminal block connections 
EPO controller board and house 
panel fuses 
Connections for the EPO system and fuses for other house panel 
components 
Dual power supplies with 
battery backup  
Provides 24 V DC power to the PLC, LED lighting, and ECS systems 
Battery backup power supply 
Provides 24 V DC power to the PLC and ECS system 
240/120 V transformer 
Provides house power to the convenience outlets 
— 
PLC 
The computer that controls the ECS system (located on the inside 
door of the control cabinet) 
 
 
HP POD 40c G2 racks 
The HP POD 40c G2 contains a total of 20 IT racks.