Life safety systems  19 
 
Manual fire pulls 
The HP POD 40c G2 includes two fire pulls. One fire pull is located next to the personnel access door and 
the second fire pull is located next to the emergency exit. 
Manually activating a fire pull does the following: 
 
Activates the POD fire alarm system horn and strobe lights 
 
Triggers a fire alarm signal to the BMS in the fire box (on page 
) and activates a 30-second delay 
before releasing the fire suppression agent 
  
 
IMPORTANT:
  The fire suppression abort button will not delay the release of the fire suppression 
agent if a manual fire pull is initiated. All personnel should evacuate immediately. 
  
 
Fire alarm indicators 
Upon activation of a fire alarm within the HP POD 40c G2, the following alarms alert personnel: 
 
Strobe lights 
Internal—The HP POD 40c G2 includes one fire strobe light located in the cold aisle. 
External—The HP POD 40c G2 includes one fire strobe light located at the standard personnel entry 
door. 
Optional—There is an additional fire strobe light located in the cold aisle that can be connected to 
the site fire alarm system at the expense of the customer. 
 
Audible horn—The HP POD 40c G2 includes two integrated horns. One horn is located on the internal 
strobe light and the second horn is located on the optional strobe light. 
 
Alarm within the ECS—The ECS system notifies you of a fire alarm condition with an alarm alert on the 
ECS screen. 
 
VESDA air sampling smoke detection system 
  
 
CAUTION: 
 Excess dust within the HP POD 40c G2 can cause the VESDA smoke detector to 
trigger a fire alarm. 
  
The VESDA system features a single zone laser scan early warning smoke detector to provide the earliest 
warning of a potential fire. 
The orange VESDA conduits that run throughout the HP POD 40c G2 include inlets for smoke sampling. The 
VESDA uses a high-efficiency aspirator to continuously draw in air from the HP POD 40c G2 and circulate 
the air through a dual-stage filter: 
 
Stage 1—Dust and dirt are removed from the air sample. 
 
Stage 2—Remaining contaminants in the air sample are removed with an ultra-fine filter. 
After the air passes through the dual-stage filter, it enters a calibrated detection chamber where a laser scans 
the air sample for the presence of smoke. When the smoke concentration reaches the first setpoint, the 
VESDA system will send an alarm signal indicating that a fire might exist. When the smoke concentration 
reaches the second setpoint, the VESDA system indicates that a fire does exist in the HP POD 40c G2 and 
sends an activation signal to the fire suppression system.