Power, electrical, and controls  27 
Feature 
Specification 
Frequency 
60 Hz 
Amps (per busway) 
200 A 
Voltage (per busway) 
415 V 
Grounding 
Copper 
Busway conductors 
3-phase + neutral + equipment ground 
 
 
Panel schedules 
The panel schedule for each electrical panel is permanently affixed to the inside cabinet door of each 
electrical panel. 
 
Wire color code 
  
 
IMPORTANT:
  UL-approved colored tape over another color of wire is only acceptable on wire 
sizes #2 and larger. 
  
120 V wiring system—Power required for the transformer in the control cabinets 
 
Wire color 
Description 
Black 
Single-phase current carrying conductor 
White 
Neutral 
Green or green and 
yellow 
 
Equipment grounding conductor 
 
Bonding conductor 
 
Earth ground 
 
415 V wiring system—Power required for the electrical busway feeders 
 
Wire color 
Description 
Brown and violet 
A Phase/L1 
Orange and violet 
B Phase/L2 
Yellow and violet 
C Phase/L3 
White and violet 
Neutral 
Green or green and 
yellow 
 
Equipment grounding conductor 
 
Bonding conductor 
 
Earth ground