HP Performance Optimized Data Center (POD) 40c 사용자 설명서
Power, electrical, and controls 27
Feature
Specification
Frequency
60 Hz
Amps (per busway)
200 A
Voltage (per busway)
415 V
Grounding
Copper
Busway conductors
3-phase + neutral + equipment ground
Panel schedules
The panel schedule for each electrical panel is permanently affixed to the inside cabinet door of each
electrical panel.
Wire color code
IMPORTANT:
UL-approved colored tape over another color of wire is only acceptable on wire
sizes #2 and larger.
120 V wiring system—Power required for the transformer in the control cabinets
Wire color
Description
Black
Single-phase current carrying conductor
White
Neutral
Green or green and
yellow
yellow
•
Equipment grounding conductor
•
Bonding conductor
•
Earth ground
415 V wiring system—Power required for the electrical busway feeders
Wire color
Description
Brown and violet
A Phase/L1
Orange and violet
B Phase/L2
Yellow and violet
C Phase/L3
White and violet
Neutral
Green or green and
yellow
yellow
•
Equipment grounding conductor
•
Bonding conductor
•
Earth ground