Environmental control system  55 
Setting the switchboard serial number 
To identify the switchboard connected to the HP POD 20c, set the switchboard serial number in the ECS: 
1. 
Select Switchboard S/N. 
A keypad appears. 
2. 
Enter the switchboard serial number. 
3. 
Select Save to store the new parameters in the system configuration file. 
 
Setting the HP POD 20c serial number 
If multiple HP POD 20c units are connected to the same facility BMS, enter each HP POD 20c serial number 
to monitor and display each HP POD 20c ECS independently through the facility BMS. 
To set the HP POD 20c serial number in the ECS: 
1. 
Select POD S/N. 
A keypad appears. 
2. 
Enter the HP POD 20c serial number. For more information, see "Parts and part number identification 
(on page 
)." 
3. 
Select Save to store the new parameters in the system configuration file. 
 
Loading default settings 
This option enables you to revert the ECS system back to the factory settings. 
  
 
CAUTION: 
 Pressing this button causes all customized ECS settings to be lost. 
  
To load the default settings: 
1. 
Select Load Default Settings. 
2. 
Select OK. 
 
Controller Settings screen 
You can only access this screen after you have entered a service-level password.