HP Performance Optimized Data Center (POD) 20cp 사용자 설명서
Cooling system 60
The minimum HP server inlet temperature is 10°C (50°F). For non-HP equipment, consult the documentation
for that equipment.
Water quality requirements and specifications
The following are the water quality requirements and specifications:
•
Closed-loop water must not contain any lime scale deposits or loose debris.
•
The temperature of the chilled water supplied to the HP POD 20c must be 12ºC to 24ºC (55ºF to 75ºF).
CAUTION:
Freezing water can cause a blockage and damage to the unit. In outside locations
that are subject to freezing temperatures, an additive such as glycol might be necessary to lower
the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP
POD 20c must be de-rated accordingly.
IMPORTANT:
The chilled water system piping and heat exchangers must be drained completely,
and then purged using compressed air when storing or transporting at or below freezing
temperatures.
temperatures.
IMPORTANT:
Operating the chilled water system at the higher end of the acceptable range
decreases the overall thermal capacity of the POD.
Acceptable water quality specifications
Water must be maintained per the following acceptable water quality standards.
Water must be maintained per the following acceptable water quality standards.
Parameter
Range
pH
8.0–10
Specific conductance at 25ºC (77ºF) 10–2500 µmhos
Alkalinity ("M" as CaCO
Alkalinity ("M" as CaCO
3
)
150–1000 ppm
Sulfur (SO
4
)
0–150 ppm
Chloride (Cl)
0–100 ppm
Hardness (CaCO
3
)
0–350 ppm
Calcium hardness (CaCO
3
)
0–200 ppm
Magnesium hardness (CaCO
3
)
0–150 ppm
Copper (Cu)
< 0.20 ppm
Iron (Fe)
< 3.0 ppm
Aluminum (Al)
< 0.50 ppm
Sodium (Na)
0–1000 ppm
Silica (SiO
2
)
0–150 ppm
Zinc (Zn)
< 1.0 ppm
Manganese (Mn)
< 0.1 ppm
Phosphate Ortho- (PO
4
)
< 3 ppm
Bacteria
< 1000 CFU/ml
Suspended solids
< 10 ppm
If your water is out of range, consult a water quality expert.
The following table describes the chilled water system specifications for the HP POD 20c.
The following table describes the chilled water system specifications for the HP POD 20c.