HP Performance Optimized Data Center (POD) 40cp 서비스 매뉴얼

다운로드
페이지 79
 
Illustrated parts catalog  12 
Item 
Component 
Description 
Dual power supplies with 
battery backup 
Provides 24 V DC power to the PLC, LED lighting, and ECS systems 
Batteries 
Provides 24 V DC power to the PLC and ECS system 
Control transformers 
Provides to the power flow control valve 
10 
240/120 V transformer 
Provides house power to the convenience outlets 
— 
PLC 
The computer that controls the ECS system (located on the inside 
door of the control cabinet) 
 
 
Cooling system component identification 
The heat exchanger access hatches are located on top of the POD. The hatches are coated with a durable 
finish to prevent corrosion. 
Side view shown 
 
 
Item 
Component 
Description 
1  
Heat exchangers 
Use facility chilled water to cool the air in the HP POD 40c NA 
2  
Heat exchanger fan 
banks 
Operate at variable speeds to maintain the preprogrammed differential 
pressure setpoint and the hot aisle temperature setpoint 
Chilled water supply  Supplies facility chilled water to cool the HP POD 40c NA 
Chilled water return 
Returns heated chilled water to the facility 
 
 
HP POD 40c NA racks 
The HP POD 40c NA contains a total of 20 IT racks. 
   
 
CAUTION: 
  If any racks contain empty RU space, use the HP POD 40c NA filler panels to 
maintain the efficiency of the HP POD 40c NA thermal system. Filler panels are available from HP 
in 10-pack quantities (part number AQ682A) and 100-pack quantities (part number AS993A). 
   
For more information about racks and network cabling, see the HP Performance Optimized Datacenter 
Networking Guide