Removal and replacement procedures  16 
Fire detection and suppression 
The fire detection and suppression system is a "Manufacturer Designed" system specifically for this HP 
product, in compliance with national standards. 
The HP standard suppression system, supplied as an optional component for the HP POD 40c NA, includes 
a Novec 1230 clean agent system. However, if the customer or local AHJ requires specific modifications or 
a replacement, HP can assist in these actions at the expense of the customer. 
HP does not certify that the fire detection and suppression system that is installed in the HP POD 40c NA 
meets all local and jurisdictional requirements. The customer is responsible for the following actions as 
related to the fire suppression system: 
• 
Verifying that the POD detection and suppression system meets local codes, including specific local 
requirements for initial and periodic inspections 
• 
Arranging for and receiving all required local permits, including initial commissioning as well as 
standard and repair maintenance 
• 
Arranging for the connection of the agent tanks, refilling of tanks, and all system testing, including 
pressure tests 
All general maintenance of the suppression system must be completed by an authorized technician. 
• 
General maintenance of the fire detection and suppression system must be completed by an authorized 
technician 
For more information, see the HP Performance Optimized Datacenter 40c NA Maintenance and 
Service guide
Additional local requirements are not covered as part of the option price or basic installation and 
deployment services, unless specifically included in an executed Statement of Work. 
 
Air filter 
There are 2 air filters per cooling zone, for a total of 12 filters. 
 
Tools are not required for installation. 
 
Removing the air filter 
1. 
Pull the locking tabs away from the air filter to release the filter.