Periodic maintenance  62 
Periodic maintenance 
Periodic maintenance overview 
Perform periodic inspections on the components in this section to ensure that the HP POD 40c NA continues 
to perform within the designed parameters. 
 
Qualified personnel 
Qualified personnel are identified as personnel who are: 
• 
Properly trained in the operation and maintenance of the HP POD 40c NA 
• 
Customer-authorized to conduct maintenance activities 
Qualified personnel can be: 
• 
HP personnel 
• 
Agents for HP 
• 
Site maintenance personnel 
 
Cooling system maintenance schedule 
 
Component to be inspected 
Task 
Frequency 
Capable Party 
Air filters 
Inspect and replace as necessary  Quarterly, or as 
needed 
Qualified personnel 
Air filter differential pressure 
sensor 
Inspect and test, replace as 
necessary 
Annually 
Qualified personnel 
Cooling system leak check 
Verify there is no visible chilled 
water leak from: 
 
Heat exchanger 
 
Cold water supply piping 
 
Cold water return piping 
If a leak is detected, see "Leak 
detection maintenance (on page 
)" 
Quarterly 
Qualified personnel 
Condensate drain pans 
Inspect pans: 
 
Free of debris 
 
No leaks 
 
Leakage detectors are in 
proper position 
Clean pans as necessary 
Quarterly 
Qualified personnel 
Condensate drain pan sensors 
Inspect and test, replace as 
necessary 
If a leak is detected, see "Leak 
detection maintenance (on page 
)" 
Quarterly 
Qualified personnel