DCP200 Profile Controller & Recorder - Product Manual
Page 88
Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Digital Input B Status
2085
0x0825
RO
Value
Digital Input B Status
0
Inactive
1
Active
Calibration Status
2086
0x0826
RO
Value
Calibration Status
0
Calibration OK
1
Calibration Required
Option Slot 1 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 1 
Module Type
2130
0x0852
RO
Value
Module Fitted In Slot 1
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
255
Error (unrecognised module)
Linear mA/V DC 
Output 1 Type
2131
0x0853
R/W
Value
Linear Output 1 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Digital Output 1 
Status
2132
0x0854
RO
Value
Digital Output 1 Status
0
Inactive
1
Active
Linear Output 1 
Level Status
2134
0x0856
RO
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Linear Output 1 
Function
2144
0x0860
R/W
Value
Linear Output 1 Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
4
Retransmit Process Variable Value
Digital Output 1 
Function
(Relays, SSR 
Drivers or Triacs. 
Linear Outputs are 
mA or VDC)
2146
0x0862
R/W
Value
Digital Output 1 Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Output 1 Alarm 
Selection
2148
0x0864
R/W
Value
Output 1 Alarm Selection
0
Alarm 1. Direct Acting