5.2 Send a record
The long set for sending to the R2600/01 can practically only be generated from the received long set at the request of a record. The function field (6th 
character) in 69h (write data) must be changed for that purpose. When copying to another R2600/01, the equipment address must be adapted (5th 
character). Following, the checksum (last but one character) must be corrected.
Send from master (control set, e.g. equipment address = 4):
Reply from R2600/01 (short set):
The record will only be accepted by the equipment, when the software version (12th character) and the length of the data block agree with the equip-
ment. The content of the data block is not checked as it is correct in itself when it comes from a R2600/01.
It must be noted to send a record only to an equipment having the same A and B markings as the equipment from which the record comes. If this is not 
observed (e.g. by impermissible configuration data) an unreasonable action of the R2600/01 may result which can be dangerous to the system.
68h
L + 6
L + 6
68h
04h
69h
D8h
01h
01h
18h
Data block
„PS“
16h
FF
PI
10h
04h
„FF“
„FF“ + 4
16h
L character