RS-485 connection
When using a RS-485 interface, as many as 32 equipment (R2600/01 and others) can be connected to the bus. 
Thereby, all terminals A, B and/or C are interconnected in parallel. The wiring must be made from equipment to equipment and must not be a star con-
nection. With longer bus lines (longer than about 5 m) the bus should be terminated at both ends with the characteristic impedance 
(e.g. 200 
Ω between A and B).
When using the 1799-V5040 interface converter on the master, the following pins are connected on the Sub-D plug:
A = 3
B = 8
C = 5
1.4 Principal function
Involved is a master/slave protocol with a fixedly assigned master (e.g. SPS) and as many as 255 slaves (equipment e.g. R2600/01). 
Communication is in half-duplex mode.
An equipment connected to the master becomes active (responds) only, when
– it receives a valid telegram addressed to itself and
– the minimum specified response delay time (t
av
) has elapsed so that the host computer has time to get ready to receive data.
Master
R2600/01
R2600/01
A
21
21
B
20
20
C
19
19