Shut OFF utility power again. The generator 
should start and the entire emergency load 
should transfer to the generator. 
Close the main breaker to restore utility power 
and allow the engine to cool down and shut 
itself OFF.
 
 
 
With the mode switch in AUTO, press the 
EXERCISER switch. Hold it down for at least 
0 seconds and release. The generator should 
start within a few seconds. The unit will run  
for about  minutes before shutting itself 
down automatically.
Once set, the generator will exercise each week 
at the same time. Be sure to show the owner 
how to set the exercise function on the day and 
time he/she wants the unit to exercise. 
 
If the battery is ever disconnected for any reason, 
the exercise function will have to be reset.
If your generator is equipped with the low 
speed exercise feature, it was enabled at the 
factory and no adjustment is needed.
 
 
 
 
As you can see, this installation is not difficult. 
Simply follow all of the instructions that come 
with the generator and observe all safety  
procedures, applicable codes and regulations.
Setting The Automatic Exercise Function