Installing the Equipment 
 
 
If the colors do not correspond with the colored markings identifying the terminals in 
a locally supplied plug, proceed as in Table 2.2. The inclusion of Table 2.2 is for 
reference. 
Table 2.2  Non Standard Supply Cord Wire Colors 
Wire Color (UK) 
Action 
green-and-yellow 
...must be connected to the terminal in the plug which is marked 
with the letter E or the safety earth symbol      or colored green or 
green-and-yellow.  
blue 
...must be connected to the terminal in the plug which is marked 
with the letter N or colored black. 
brown 
...must be connected to the terminal in the plug which is marked 
with the letter L or colored red. 
2.5.3 
Connecting the Equipment to the AC Power Supply 
As there is no mains power switch fitted to this unit, ensure the local AC power 
supply is switched OFF before connecting the supply cord. 
Connect the mains lead to the equipment and then to the local supply. 
2.6 
Protective Earth/Technical Earth 
Warning! 
This unit must be correctly earthed through the molded plug supplied. If the local 
mains supply does not have an earth conductor do not connect the unit. Contact 
Ericsson Customer Services for advice. 
Before connecting the unit to the supply, check the supply requirements in Annex B
The terminal marked    at the rear panel is a Technical Earth. Its use is 
recommended. This is NOT a protective earth for electric shock protection. The 
terminal is provided to: 
•  Ensure all equipment chassis fixed within a rack are at the same technical earth 
potential. To do this, connect a wire between the Technical Earth terminal and a 
suitable point on the rack. 
•  Eliminate the migration of stray charges when connecting between equipment.  
The Technical Earth provides a suitable connection between the equipment and the 
installation to give a low impedance path at normal operating frequencies. 
 
 
 
EN/LZT 790 0003/2 R1A
 