Piping
31
Liebert
®
 MC
Figure 21 Piping: dimensions—dual circuit two-fan and four-fan units
Table 8
Piping: dimensions—dual-circuit, two-fan and four-fan units
Model #
# of
Fans
Connection Sizes, OD, in
Hot Gas Line
Liquid Line
MCM080
2
7/8
5/8
MCL110
2
1-1/8
7/8
MCM160
4
1-1/8
7/8
MCL220
4
1-3/8
1-1/8
Source: DPN002425, Rev. 3
Optional fusible plug service kit to
be brazed into the liquid line(s) in
either the vertical or horizontal
position. (where required)
(vertical position is preferred,
horizontal position is optional.)
for two circuit systems, one
fusible plug kit will need to
be installed in each circuit.
Circuit #2
Circuit #1
Horizontal
Leaving Liquid
Line
Vertical
Field Piping
Entering Hot
Gas Line
Inverted traps in refrigerant
lines are internal to
the condenser. Do not trap
external to the unit.
DPN002425
Rev. 3