Isys
®
 G-Series Touchpanel Interface
 
Operations Guide – DOC. 6501 
Isys
®
 G-Series Touchpanel Interface: TPS-GA-TPI  
  33 
Serial Connection 
1. Connect 
the 
RGBHV OUT to the RGB in on the touchscreen. 
2.  Connect to the TPS-GA-TPI via USB or TCP/IP communication as described in 
3.  Using the Toolbox Text Console, enter the EXTT command to set the  
TPS-GA-TPI for the touchscreen you have connected.  
4.  Using the Toolbox Text Console, enter the TPIMODE command to set the 
TPS-GA-TPI to the native resolution of the touchscreen. Refer to the 
touchscreen documentation to determine its native resolution. 
5.  Confirm that RS-232 is set to External Touch Input. Refer to “RS-232 Menu” 
on page 21. 
6.  Attach a serial cable assembly between the touchscreen and the TPS-GA-TPI.  
7.  Reboot the TPS-GA-TPI and the touchscreen. 
CAUTION: Make sure the USB mouse is not attached when you calibrate the 
touchscreen. Calibrating the touchscreen with the mouse attached may cause the 
system to become unstable. 
NOTE: Some non-Crestron touchscreens require that the “pen” supplied with the 
touchscreen be used during calibration. Simply touching the screen with your finger 
will not work. 
8.  Calibrate the touchscreen by selecting Functions | Setup Mode | Enter 
Calibration Mode in the Toolbox System Info window. 
USB Connection 
1. Connect 
the 
RGBHV OUT to the RGB in on the touchscreen. 
2.  Connect to the TPS-GA-TPI via serial or TCP/IP communication as described in 
3.  Using the Toolbox Text Console, enter the EXTT command to set the  
TPS-GA-TPI for the touchscreen you have connected. 
4.  Using the Toolbox Text Console, enter the TPIMODE command to set the  
TPS-GA-TPI to the native resolution of the touchscreen. Refer to the 
touchscreen documentation to determine it’s native resolution. 
5.  Attach a USB cable assembly between the touchscreen and the TPS-GA-TPI. 
6.  Reboot the TPS-GA-TPI and the touchscreen. 
7.  Calibrate the touchscreen by selecting Functions | Setup Mode | Enter 
Calibration Mode in the Toolbox System Info window.