In all these cases the output voltage of the UPs is supplied by the emergency 
bypass line through the static bypass commuter switch (Fig. 12), provided that the 
ePO is inactive.
3.3.4. oPEratioN iN maNUal byPass 
When we wish to perform some maintenance check on the device, it may be 
disconnected from the mains without any need to cut the power supply to the 
system and affect the critical load. The UPs may be altered, only by technical or 
maintenance personnel. For maintenance bypass follow the special instructions  
for that purpose (refer chapter 5.4).
3.4. ParallEl oPEratioN
2 UPs’s can be paralleled to one UPs system for redundancy purposes or to 
double the maximal load level. Only identical UPs with the same ratings can  
be paralleled. Fig.13 shows the single line diagram of a parallel system of  
Protect 2.33 2.0 showing the power connections and the control bus cables.  
Two UPs running in parallel always do load-sharing. Parallel operation offers  
several advantages like higher availability or “modular” adaption of the UPs 
system to cover increasing power demands.
The parallel system management is based on a dynamic MasTer-slaVe principle, 
where the first UPs in normal operating mode will become MasTer. It has the 
control of the second UPs (slaVe).
Fig.13:  Single line diagram for UPS parallel system