2-4 SANnet II 200 FC, SATA, and SATA SE Array Installation, Operation, and Service Manual • March 2005
2.5
Physical Specifications
Use the physical specifications in Table 2-3 to plan the location of your array.
2.6
Layout Map
It is helpful to create a sketch or layout map to indicate the exact location of the array 
as well as the location of the hosts, console, and Ethernet connections that will be 
connected to it. 
As you lay out the components, consider the cable lengths that will be used. 
2.6.1
Rack Placement
Follow these guidelines when preparing a rackmount placement for your system:
Ensure that the floor surface is level.
Leave enough space in front of the rack to access components for servicing.
Leave enough space in back of the rack to access components for servicing. 
Keep power and interface cables clear of foot traffic. Route cables inside walls, 
under the floor, through the ceiling, or in protective channels or raceways.
Table 2-2  Power Specifications 
AC power 
Voltage and frequency 90 to 264 VAC, 47 to 63 Hz
Input current 
5A max
Power supply output voltage
+5 VDC and +12 VDC
DC power
–48 VDC (
36 VDC to 
72 VDC)
Table 2-3  Physical Specifications
Category
Description
Dimensions
2U 3.45 inches (8.76 cm.) height 
21 inches (53.34 cm.) chassis depth
17.5 inches (44.6 cm.) width
19 inches (48.26 cm.) width with ears
Installation 
clearances
For FRU component removal and replacement, 15 inches (37 
cm) is required front and back.
Cooling clearances
6 inches (15 cm) is required front and back. No cooling 
clearance is required on the sides or the top and bottom of the 
array.