Table 2 – AHRI COOLING RATING TABLE 1--STAGE COOLING
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER (kW)
SEER
EER
IEER
04A
1
3
34.6
3.1
13.00
11.00
N/A
05A
1
4
45.0
4.0
13.00
11.00
N/A
06A
1
5
59.0
5.5
13.00
10.75
N/A
07A
1
6
70.0
6.4
N/A
11.00
11.2
08A
1
7.5
88.0
8.0
N/A
11.00
11.2
09A
1
8.5
97.0
8.8
N/A
11.00
11.2
12A
1
10
117.0
10.6
N/A
11.00
11.2
Table 3 – AHRI COOLING RATING TABLE 2--STAGE COOLING
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER (kW)
SEER
EER
IEER
08D
2
7.5
83.0
7.5
N/A
11.00
11.7
09D
2
8.5
99.0
9.0
N/A
11.00
11.7
12D
2
10
114.0
10.3
N/A
11.10
11.8
14D
2
12.5
140.0
12.9
N/A
10.80
11.0
LEGEND
AHRI
--- Air Conditioning, Heating and Refrigeration
Institute Test Standard
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER
--- Energy Efficiency Ratio
IEER
--- Integrated Energy Efficiency Ratio
SEER
--- Seasonal Energy Efficiency Ratio
Use of the AHRI Certified TM
Mark indicates a manufacturer’s  
participation in the program For
verification of certification for
individual products, go to 
www.ahridirectory.org. 
NOTES:
1. Rated in accordance with AHRI Standard 210/240 or
340/360, as appropriate.
2. Ratings are based on:
Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb
indoor air temp and 95_F (35_C) db outdoor air temp.
IEER Standard: A measure that expresses cooling
part---load EER efficiency for commercial unitary air
conditioning and heat pump equipment on the basis of
weighted operation at various load capacities.
3. All 580J units comply with ASHRAE 90.1 Energy
Standard for minimum SEER and EER requirements.
4. 580J units comply with US Energy Policy Act (2005).
To evaluate code compliance requirements, refer to
state and local codes or visit the following website:
http://bcap---energy.org.