2.7.  Connecting External Alarms 
2.7.1.  Overview 
The SZ monitor includes four SPDT relays whose contacts are rated 2 A at 250 VAC (inductive) and 5 A 
at 250 VAC (resistive). These relays are used for the connection of external alarm devices that are 
activated when the relay is energized. The relays are factory assigned to energize under the following 
conditions: 
 
Relay #1 
Leak 
Alarm Point 100 ppm 
 
Relay #2 
Spill 
Alarm Point 300 ppm 
 
Relay #3 
Evacuate 
Alarm Point 500 ppm 
 
Relay #4 
Fault 
System Fault Event 
 
 
NOTE:  Alarm points of relays #1, #2, and #3 are set using the monitor’s LEAKLVL
SPILLLVL, and EVACLVL function screens (page 22). 
 
2.7.2.  Connection 
Use any of the service knockouts to gain cable access to the interior of the monitor. Locate the External 
Alarm Relay Connector (page 11). Secure the leads from the external alarm device and its power source 
to the connector as shown in the diagram below.  
 
Figure 2-8.  External Alarm Relay Connector 
 
Each relay may be connected as normally open (NO), or normally closed (NC). 
The relay contacts are rated 2 A at 250 VAC (inductive) and 5 A at 250 VAC (resistive). 
Power  for the alarm devices connected to the relay contacts may be supplied by an external 24 V DC 
power source or the monitor’s AC input terminals. 
In  Figure  2-9, power to this device is being tapped off the monitor’s AC input.  In  Figure  2-10,  power is 
supplied from an external power source