Security Escort | Technical Reference Manual | 3.0  System Menus 
and Screens 
EN | 16 
 
 
Bosch Security Systems | 6/12 | 38947D 
 
Enable Reed Switch 
If checked, the reed switch input of 
this transmitter is enabled and causes 
an alarm. Otherwise, the reed switch 
input is disabled. The alarm group this 
transmitter is assigned to must be 
armed, for this input to cause an 
alarm, which is displayed. If no alarm 
group is assigned, the transmitter is 
always armed. To enable this option, 
the transmitter’s class must be set to 
point type. 
Optional Text 
This is optional text that can be added 
to the location text when this input 
reports an alarm. To enable this 
option, the transmitter’s class must be 
set to point type. 
Disable Shorted Loop 
If selected, a shorted loop on this 
transmitter does not cause an alarm or 
trouble report to display. To enable 
this option, the transmitter’s class 
must be set to point type. 
Alarm on Shorted Loop 
If selected and the alarm group this 
transmitter is assigned to is armed, a 
shorted loop on this transmitter causes 
an Alarm Report to display. For this 
input to cause an alarm, the alarm 
group this transmitter is assigned to 
must be armed, which is displayed. If 
no alarm group is assigned, the 
transmitter is always armed. To enable 
this option, the transmitter’s class 
must be set to point type. 
Trouble on Shorted Loop  
If selected, a shorted loop on this 
transmitter causes a Trouble Report to 
display. To enable this option, the 
transmitter’s class must be set to 
point type. 
Alarm When Armed, Trouble When Disarmed 
on Shorted Loop 
If selected and the alarm group this 
transmitter is assigned to is armed, a 
shorted loop on this transmitter causes 
an Alarm Report to display. If selected 
and the alarm group this transmitter is 
assigned to is disarmed, then a shorted 
loop on this transmitter causes a 
Trouble Report to display. If no alarm 
group is assigned, the transmitter is 
always armed. To enable this option, 
the transmitter’s class must be set to 
point type. 
Disable Open Loop 
If selected, an open loop on this 
transmitter does not cause an Alarm or 
Trouble Report to display. To enable 
this option, the transmitter’s class 
must be set to point type. 
Alarm on Open Loop 
If selected and the alarm group this 
transmitter is assigned to is armed, an 
open loop on this transmitter causes an 
Alarm Report to display. The alarm 
group this transmitter is assigned to 
must be armed for this input to cause 
an alarm, which is displayed. If no 
alarm group is assigned, the 
transmitter is always armed. To enable 
this option, the transmitter’s class 
must be set to point type. 
Trouble on Open Loop  
If selected, an open loop on this 
transmitter causes a Trouble Report to 
display. To enable this option, the 
transmitter’s class must be set to 
point type. 
Alarm When Armed, Trouble When Disarmed 
on Open Loop 
If selected and the alarm group this 
transmitter is assigned to is armed, an 
open loop on this transmitter causes an 
Alarm Report to display. If selected 
and the alarm group this transmitter is 
assigned to is disarmed, an open loop 
on this transmitter causes a Trouble 
Report to display. If no alarm group is 
assigned, the transmitter is always 
armed. To enable this option, the 
transmitter’s class must be set to 
point type. 
Fixed Location and Pager Text 
This is the text that displays as the 
location of the alarm for fixed 
location transmitters and on pagers 
reporting this alarm. 
Transponder Name 
Select the transponder with the area 
that defines the area for a wandering 
(virtual fence) alarm. Refer to 
Transponder Area for the operation and 
setup of the wandering alarm (virtual 
fence alarm).