Bosch Appliances Network Router D6100 사용자 설명서

다운로드
페이지 168
Conettix D6600/D6100 | Computer Interface Manual | 3.0  
Computer Communication Protocols 
 
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 
29 
 
3.2.2 
Ademco Contact-ID (Message Type a) 
SIA Mode Description 
Contact-ID 
Example 
<LF><CRC><a><sequence#><receiver#><line#>[#aaaa|18QXYZGGCCC]<CR> 
 
Table 39: 
Ademco Contact-ID (Message Type a) Byte Description 
 
Title Description 
LF 
Standard line feed character.  
CRC 
Cyclical redundancy check number.  
Message Type 
a  
sequence# 
The message sequence number. The valid sequence number range is 0001 to 9999. 
receiver# 
The receiver gateway that sent the message. Valid digits are 01 to 99 for the 
D6600/D6100. 
line# 
(Line/Group #) 
The line number of the line in the receiver gateway that sent the message. Valid digits are 00 
to 99. The receiver uses Line 0 (zero) for internal messages. 
account# 
The communicator's account number has four digits. 
18 
Ademco Contact-ID format number. 
Qualifier, 1 = New event or opening, 3 = New restore or closing, 6 = Previous event.  
XYZ 
Class code and event code (refer to Appendix A: Contact ID Event Code Classifications on 
page 53).  
GG 
Group number.  
CCC 
Zone codes or User ID.  
 
Figure 8: 
Message sent to printer 
mm/ddshh:mmsLxxsCIDsACCTsaaaa+++sACCsa
aaasNNNsEVENT=XYZsG=GGsC=CCC
 
 
 
For lines that are grouped, Gxx appears 
instead of Lxx. 
 
Table 40: 
Ademco Contact-ID (Message Type a) 
Printer Output 
 
Characters Description 
CID 
Contact-ID format. 
Gxx Grouped 
Line 
numbers. 
Lxx 
Line number. 
NNN 
If Q = 1, print E/O for new event or 
opening  If Q = 3, print R/C for restore or 
closing  If Q = 6, print “OLD” for old 
messages and events.