D9412GV2/D7412GV2 | Program Entry Guide | 1.0 Introduction
EN | 10
Bosch Security Systems, Inc. | 10/08 | F01U003636-04
Table 5: UL 864 Programming Requirements (continued)
Product Feature/Option Permitted in
UL 864? (Y/N)
Possible Settings Settings Permitted in
UL 864
Refer to
Page:
Page:
For IP Communications to a D6600 Receiver
Enhanced Comm
Enhanced Comm
Yes
Yes / No
Set to Yes
Path1 IP Add1 (2, 3 or 4)
Yes
000 to 255
Program a valid IP
address
address
− 136
Path 1 Poll Rate
Yes
0, 5 to 65535 sec
Program as necessary
Path 1 Ack Wait
Yes
0, 5 to 65535 sec
Program as necessary
Path 1 Retry Count
Yes
0 to 255
Program as necessary
9133 Supervision
Yes
Yes / No
Set to Yes
The following programmable parameters are recommended by Bosch when installing a commercial fire alarm
system. Always check with your local Authority Having Jurisdiction.
system. Always check with your local Authority Having Jurisdiction.
Table 6: UL 864 Programming Recommendations
Prompt Possible
Settings
Recommendation
Phone Line Fail Report
Yes / No
Yes
Phone Line Restoral Report
Yes / No
Yes
Fire Walk Start Report
Yes / No
Yes
Fire Walk End Report
Yes / No
Yes
Cancel Report
Yes / No
Yes
CC# Scope
Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Wide, Custom, No Keypad
Do not program No Keypad
CC# EnhancCmdCtr
Yes / No
Set to Yes, if applicable
CC# Menu Key Lock
Yes / No
If using D1256RB, set to No
Reset Sensors
Disable/Enable/Passcode Protect
Enable
Fire Test
Disable / Enable / Passcode Protect Enable
L## Reset Sensors
Disable / Enable
If Reset Sensor is set to Passcode
Protect, set this to Enable
Protect, set this to Enable
L## Fire Test
Disable / Enable
If Fire Test is set to Passcode
Protect, set this to Enable
Protect, set this to Enable
U### User Group
Blank, 1 to 8
Program as blank
P## Ring Til Rst
Yes / No
May be required for Waterflow,
otherwise No
otherwise No
P## Cross Point
Yes / No
Set to No for Fire devices.
D# Fire Unlock
Yes / No
No