D9412GV2/D7412GV2 | Program Entry Guide | 6.0  GV2AUX 
EN | 136 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
 
Path # IP Add4 
Default: 
Selection: 
0 to 255 
Refer to Path 1 IP Add1
Path # PortNum 
Default: 
7700 
Selection:  1 to 65535 
This prompt specifies the destination port number for 
each of the four enhanced communication route path 
destinations. All four IP address-and-port pairs must 
be unique to ensure that event acknowledgments are 
accounted correctly. Duplicate address-and-port pairs 
are not supported. 
Path # Poll Rate 
Default: 
Selection: 
0, 5 to 65535 sec 
Disables the heartbeat poll (not 
recommended, refer to the first 
Important Note that follows). 
5 to 65535 
Enables the poll rate for the amount 
of time programmed here. 
This prompt and the next two prompts determine how 
the SDI Path is supervised between the SDI device 
and the central station receiver(s). Do not confuse 
the SDI Path supervision with the supervision of the 
SDI device itself (the connection of the SDI device to 
the control panel). Each SDI Path can be configured 
to transmit a Heartbeat Poll to the central station for 
supervision purposes. This ensures the integrity of 
the connection at all times. 
 
If using IP Addresses as the 
communication means for UL 864 
Commercial Fire applications, program 
this parameter as necessary. 
 
 
 
 
When sending reports to a central station 
receiver over a network path, you must 
set Path # Poll Rate to a non-zero value. 
Failure to program a value into this field 
could prevent a failed network 
communications path from restoring to 
normal. 
 
If the control panel is programmed to 
send Heartbeat Poll to the central station, 
a rate of 75 sec maintains the virtual link 
 
in most network configurations. 
Decreasing the value for Path # Poll 
Rate
 increases the amount of idle 
communication between the SDI device 
and the central station receiver. 
Increased idle communication between 
the control panel and the receiver 
decreases the control panel’s event 
reporting efficiency. 
 
The control panel readjusts the Heartbeat 
Poll rate temporarily to less than 300 sec 
to 300 sec when online with RPS. The 
 
poll rate returns to the programmed value 
after the RPS session ends. 
The value programmed in Path # Poll Rate is the 
interval at which the control panel sends a Heartbeat 
Poll to the central station receiver. The value 
programmed in Path # Ack Wait is the length of time 
the control panel waits for an acknowledgment of a 
Heartbeat poll. If the acknowledgment is not 
received, the control panel checks to determine if the 
Path # Retry Count entry is greater than 0. If so, the 
control panel retries the number of times 
programmed (in Path # Retry Count) to send the 
Heartbeat Poll before declaring the Path failed and 
generating a COMM FAIL SDI ## (Path 1 = SDI 88, 
Path 2 = SDI 89, Path 3 = SDI 90, Path 4 = SDI 91) 
Event.  
If Path # Poll Rate is programmed with a value and 
the central station does not acknowledge the poll 
from the control panel, keypads annunciate a trouble 
condition. To send this event to the central station, 
refer to the Comm Fail prompt in Section 2.13.2 
Panel-Wide Relays
 on page 81
Example of Heartbeat:  
• 
• 
• 
Path # Poll Rate is set to 120 sec 
Path # Ack Wait time is set to 10 sec 
Path # Retry Count is set to 2